Switching distances
Operating distance for center offset m = 0
(only in combination with CES-A-BBA actuator)
Parameter Value Unit
min. typ. max.
Switch-on distance - 18 -
mm
Assured switch-on distance s
ao
1)
15 - -
Switching hysteresis
1)
1 3 -
Assured switch-off distance s
ar
- - 45
1) The values apply for surface installation of the actuator.
Typical operating distance
(only in combination with CES-A-BBA actuator)
X
25
15
20
10
5
20
25
30
5
10
15
-30
30
-30
25
20
15
10
5
Y
Z
For a side approach direction for the actuator and safety switch, a minimum distance of s = 4 mm
must be maintained so that the operating distance of the side lobes is not entered.
Figure 5: Typical operating distance