More than safety.Operating InstructionsNon-Contact Safety SwitchCES-AP-C01-AH (Unicode)

Strany 2 - Contents

Operating Instructions Safety Switch CES-AP-C01-AH10Important!If the device does not appear to function when operating voltage is applied (e.g. green

Strany 3 - Correct use

Operating Instructions Safety Switch CES-AP-C01-AH11Safety in case of faults Ì The operating voltage UB is reverse polarity protected. Ì The contacts

Strany 4

Operating Instructions Safety Switch CES-AP-C01-AH12Requirements for connection cablesCaution!Risk of damage to equipment or malfunctions as a result

Strany 5 - General safety instructions

Operating Instructions Safety Switch CES-AP-C01-AH13ConnectionImportant!The subsystem CES-AP complies with PL e in accordance with EN 13849-1. To inte

Strany 6 - Function

Operating Instructions Safety Switch CES-AP-C01-AH14Warning!In the event of a fault: Loss of the safety function due to incorrect connection. Ì To ens

Strany 7

Operating Instructions Safety Switch CES-AP-C01-AH15SetupLED indicatorsLED Color State SignificanceSTATEgreenillumi-natedNormal operationflashing- Door

Strany 8 - Mounting

Operating Instructions Safety Switch CES-AP-C01-AH16Functional checkAfter installation and any fault, the safety function must be fully checked. Proce

Strany 9 - Electrical connection

Operating Instructions Safety Switch CES-AP-C01-AH17System status tableOperating modeActuator/door posi-tionSafety outputs OA and OBLED indicator, out

Strany 10

Operating Instructions Safety Switch CES-AP-C01-AH18Technical dataNote:If a product data sheet is included with the product, the information on the da

Strany 11 - Safety in case of faults

Operating Instructions Safety Switch CES-AP-C01-AH19Typical system timesReady delay: After switching on, the unit carries out a self-test for 500 ms.

Strany 12 - 5-pin, pin 5 not used

Operating Instructions Safety Switch CES-AP-C01-AH2ContentsAbout this document 3Correct use 3Possible combinations for CES components 4Exclusion of

Strany 13 - Connection

Operating Instructions Safety Switch CES-AP-C01-AH20Technical data for actuator CES-A-BBAParameter Value Unitmin. typ. max.Housing material Fortron, r

Strany 14 - M12 plug-connector

Operating Instructions Safety Switch CES-AP-C01-AH21Switching distancesOperating distance for center offset m = 0(only in combination with CES-A-BBA a

Strany 15 - LED indicators

Operating Instructions Safety Switch CES-AP-C01-AH22Technical data for actuator CES-A-BPAParameter Value Unitmin. typ. max.Housing material PBTDimensi

Strany 16 - Functional check

Operating Instructions Safety Switch CES-AP-C01-AH23Switching distancesOperating distance for center offset m = 0(only in conjunction with actuator CE

Strany 17 - System status table

Operating Instructions Safety Switch CES-AP-C01-AH24Technical data for actuator CES-A-BRNParameter Value Unitmin. typ. max.Housing material PPSDimensi

Strany 18

Operating Instructions Safety Switch CES-AP-C01-AH25Switching distancesOperating distance for center offset m = 0(only in combination with actuator CE

Strany 19 - Dimension drawing

Operating Instructions Safety Switch CES-AP-C01-AH26Ordering information and accessoriesDesignation Version Order No.CES-AP-C01-AH-SB-111145 Plug conn

Strany 20

Operating Instructions Safety Switch CES-AP-C01-AH27ServiceIf service support is required, please contact:EUCHNER GmbH + Co. KGKohlhammerstraße 16D-70

Strany 21 - Typical operating distance

Operating Instructions Safety Switch CES-AP-C01-AH28Declaration of conformity

Strany 22

Operating Instructions Safety Switch CES-AP-C01-AH29

Strany 23

Operating Instructions Safety Switch CES-AP-C01-AH3About this documentThis document is valid for all safety switches CES-AP-C01-AH with version number

Strany 24 - Active face

More than safety.Euchner GmbH + Co. KGKohlhammerstraße 16D-70771 [email protected]:112663-04-10/13Title: Ope

Strany 25

Operating Instructions Safety Switch CES-AP-C01-AH4Possible combinations for CES componentsSafety switchesActuatorCES-A-BBA071840CES-A-BPA098775CES-A-

Strany 26 - Inspection and service

Operating Instructions Safety Switch CES-AP-C01-AH5General safety instructionsSafety switches fulfill personal protection functions. Incorrect installa

Strany 27

Operating Instructions Safety Switch CES-AP-C01-AH6FunctionThe device complies with the following safety requirements: Ì Category 4, PLe according to

Strany 28 - Declaration of conformity

Operating Instructions Safety Switch CES-AP-C01-AH7Changing the approach directionCaution!Risk of damage to equipment as a result of trapped cables. Ì

Strany 29

Operating Instructions Safety Switch CES-AP-C01-AH8MountingImportant! Ì From the assured switch-off distance Sar, the safety outputs are safely shut d

Strany 30 - More than safety

Operating Instructions Safety Switch CES-AP-C01-AH9Electrical connectionWarning!In the event of a fault: Loss of the safety function due to incorrect