Operating Instructions Safety Switch CES-AP-C.2-CH
14
Warning!
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (OA and OB) must always be evaluated.
Single-channel use of the safety outputs leads to a loss of the category in
accordance with EN ISO 13849-1.
GND
DC 24 V
CES-AP-C.2-...
UB1
OA2
OB4
NC6
M8 plug-connector
(6-pin)
OUT5
0V3
-K1
-K2
-M1 -M2
M M
A1
A2
A1
A2
13
14
13
14
Fig. 4: Example of incorrect connection.
Connecting a CES-AP-...-SB-... (pin 5 not assigned)
to a decentralized peripheral system (e.g. ET200pro
series from Siemens)
Observe the information in the section Particularities for operation on decentralized
peripheral systems on page 10 before connecting the device.
Fig. 5: Connection example for connection to decentralized peripheral systems
CES-AP-...-SB-...
UB1
FO1A2
0V3
FO1B4
S1: M12 plug-connector
(5-pin)
n.c.5
decentralized
periphery
e.g. ET 200pro
PLC
DI
1
5
2
4
3
1
5
2
4
3
DO