Operating Instructions Safety Switch CES-AR-C01-CH-SA
21
System status table
Operating mode
Actuator/door posi-
tion
Safety outputs OA
and OB
LED indicator,
output
State
STATE (green)
DIA (red)
Self-test
X off
10 Hz
(8 s)
Self-test after power up
Normal operation
closed on
Normal operation, door closed
closed on
flashes
quickly
2 Hz
Normal operation, door closed, actuator in limit range ¨ Re-adjust door (V. 1.1.2 or higher)
closed off
1 x in-
verse
Normal operation, door closed, preceding device in the switch chain signals "door open" (only with
series connection)
open off
1 x Normal operation, door open
Fault display
X off
2 x Input fault (e.g. missing test pulses, illogical switch state from previous switch in the switch chain)
closed off
3 x Defective actuator (e.g. fault in code or code not readable)
X off
4 x
Output error
(e.g. short circuits, loss of switching ability)
X off
5 x Internal fault (e.g. component faulty, data error)
X off X X Internal fault with door fault
Key to symbols
LED not illuminated
LED illuminated
10 Hz (8 s)
LED flashes for 8 seconds at 10 Hz
3 x
LED flashes three times, and this is then repeated
X Any state
After the cause has been remedied, faults can generally be reset by opening and
closing the door. If the fault is still displayed afterward, use the reset function or
briefly interrupt the power supply. Please contact the manufacturer if the fault could
not be reset after restarting.
Important!
If you do not find the displayed device status in the System status table, this indi-
cates an internal device fault. In this case, you should contact the manufacturer.